12.6.1 Procedure - Changing the Window on All Screens

The Global Window changes depending on the value stored in a word address (for example, D117).

  1. From the [Project] menu, select [System Settings], and click [Display Unit] to open the [Mode] tab.

  2. From [Global Window Operation], select [Indirect].

  3. Set the [Data Type].

  4. Select the [System Area] tab.

  5. In [System Area Device], select the appropriate device/PLC that uses the system area. In [System Area Start Address], define the top address (D100).

  6. Select the following check boxes: [Enable System Data Area], [Window Control], [Window Screen], and [Window Display Position].

    The Global Window (Indirect) settings are complete.

Operating Procedure

Set the window number you want to display in [Window Number] address (D117), and the display coordinates in the [Window Display Position] address (D118, D119) to turn ON bit 0 for the [Window Control Address](D116).