T.8.3 When PROFIBUS is used

Error Code

Error Message

Solution

RHxx128

PROFIBUS master is not in RUN mode or Packet interpreter program (FB99) is not running.

Check the condition of the connected device or if FB99 has been called.

RHxx129

Packet interpreter program (FB99) from PLC reports address error (Address:Device address).

Check the device described in the error message.

RHxx130

Packet interpreter program (FB99) from PLC reports device error (Address:Device address)

Check if the size of the data block is set within the allowable range in the device/PLC settings.

RHxx131

Packet interpreter program (FB99) from PLC reports command error (Address:Device address)

Check if the input device is set to write in the project file settings.

RHxx132

Packet interpreter program (FB99) from PLC reports command error (Address:Device address)

Restart the system. If there is no improvement, contact customer support.

T.10.2 Telephone Contact

RHxx144

Waiting for PROFIBUS master

Check if the master unit's power is ON and the cable is properly connected.

RHxx145

Wrong configuration received from PROFIBUS master.

Check the I/O settings of the master and of the slave.

RHxx146

Watchdog failed

Check the connection to the connected device.

RHxx147

Unknown error.

Restart the system. If there is no improvement, contact customer support.

T.10.2 Telephone Contact

RHxx148

Wrong parameter data received from PROFIBUS Master

Compare User_Pm_Data with the original unchanged GSD file.