T.7.3 When the DIO board type GP3000 series is used

I/O driver errors

Error Code

Error Message

Cause and Troubleshooting

RGEE002

Setting value error

The data type of the symbol variable assigned to the I/O is illegal. The I/O setting value is illegal. When this error occurs, transfer the program again.

RGEE003

Device out-of-range error

The address of the symbol variable assigned to the I/O is out of range. When this error occurs, transfer the program again.

RGEE004

Duplicate terminals

The number of I/O terminals exceeds the limit (6 bit inputs and 2 bit outputs). When this error occurs, transfer the program again.

RGEE005

Terminal setting order error

The I/O terminal numbers are not specified in ascending order. When this error occurs, transfer the program again.

RGEE006

Insufficient number of terminal registration

The number of I/O terminals is not appropriate (insufficient). When this error occurs, transfer the program again.

RGEE009

Repeat driver setting

The driver has been registered twice. When this error occurs, transfer the program again.

RGEE011

Bit/Word format mismatch

The variable type specified in the I/O is incorrect. Transfer the project data again.

RGEE012

Setting level value error

Something is wrong with the I/O driver. Transfer the project data again.

RGEE013

Data obtaining address error

The I/O driver information is incorrect. Transfer the project data again.
The controller information is incorrect. Transfer the project data again.

RGEE014

Driver/Unit unregistered

The I/O driver or I/O is not registered. Transfer the project data again.

RGEE050

I/O board ID mismatch

The I/O board being connected is different from the I/O board in the project. Transfer the project data again.

RGEE100

Input chatter

Chattering occurred during the input from the DIO board. This may be caused by noise or GP unit failure. If this error occurs frequently, the unit may be faulty. Please contact customer support. This error code continues to appear until the controller is reset.

RGEE101

DIO write error

Although data was sent to the DIO board, it was not output when the output result was fed back. This may be caused by noise or GP unit failure. If this error occurs frequently, the unit may be faulty. Please contact customer support. This error code continues to appear until the controller is reset.

Runtime errors

The following error messages are displayed while the logic program is running.

Error Code

Error Message

Cause and Solution

RGAA001

Watchdog error

The possible causes are that the operation has entered an endless loop in the program, or that the program uses many instructions which wait for logic programs. With GP-Pro EX, select [Display Unit] in the [System Settings], open the [Logic Settings] tab, and set the time for [WDT (Watchdog Timer) Settings] longer.