T.3.11 A screen prompting you to re-transfer appears after you have transferred the file

Does the transfer screen appear again after you finish transfer and restart the unit?

Cause

For the GP-3300 Series, when the [Revision] selected in [Model] is [Greater Than Or Equal To Rev*-4], and the revision for the receiving display unit is earlier than Rev 4, transfer fails. Unable to transfer even downloading using the memory loader of external storage.

However, for AGP-3310T/3360T, transfer is possible regardless of revision.

Solution

This problem occurs when you create a new project and select [GP-33** Series] as the [Display Unit] and [Before Rev*-4] for the [Revision], and you add functions that are not supported by display unit models Rev 3 or earlier. As a result, transfer fails.

In the [System Settings] [Display] tab, click [Change Display Unit] and set [Revision] to [Before Rev*-4]. Then, delete all functions that are not supported by models before Revision 4, and perform transfer.

The following are functions that are not supported by models before Revision 4.