>2007 > February 5 Important Note on using GP-Pro EX Ver. 1.10We appreciate your patronage of our products. OutlineThe issue is that GP3000 unit does not work after a backup file, created by Memory Loader Tool Function in GP-Pro EX Ver. 1.10, has been downloaded to the unit by CF card. Affected CustomersCustomers who have purchased GP-Pro EX Ver. 1.10 Occurrence ConditionThe issue occurs when all the following 3 conditions are met.
(How to check the version) When switched on, the GP3000 unit shows the OS Core Program version.
Start up Firmware (Ver *.*.*)
Searching Bootable Image Checking Hardware Loading System DescriptionWhen a backup file created by Memory Loader Tool Function is downloaded to the GP3000 unit listed above by CF card, and the above 3 conditions are met, the GP3000 unit becomes inoperative. (The screen remains black.) The above issue will not occur under the following circumstance;
Request to users when this issue occursPlease contact our sales office in your country or region. For contact information, please visit the following site. URL: http://www.pro-face.com/otasuke/support_info.htm Avoidance MethodBy updating to the latest version (Ver. 1.10.200) of GP-Pro EX Ver. 1.10, it is possible to prevent the above issue.
Start up the GP-Pro EX Ver. 1.10, and select [Help (H)] in the menu bar → [Confirm Update of GP-Pro EX (U)].
Download the update module from the following website and update your GP-Pro EX Ver. 1.10 using the module.→ GP-Pro EX Ver. 1.10.200 Update * Membership Registration (free) is required for our support site "Otasuke Pro!" NOTE:The backup data, which has already been saved in CF card, needs to be recreated with the latest version (Ver.1.10.200). Otherwise, this issue will occur. Sorry for the inconvenience, but please recreate the backup data to avoid the issue. For the information on how to create backup data, please refer to the Manual. How to confirm the update is properly doneConfirm the versions of your GP-Pro EX and Memory Loader Tool.
Start up the GP-Pro EX Ver. 1.10, and select [Help(H)]in the menu bar →[Version Info(A)].
After the update is completed, check the version of GP-Pro EX and make sure V1.10.200 or later is installed.
Start up the Memory Loader Tool, and check the version written at the bottom left of the screen.
After the update is completed, check the version of Memory Loader Tool and make sure Ver. 1.0.3 or later is installed. For any inquiryIf you have any inquiry, please contact our sales office in your country or region. |