Information to our valued customers who use MODBUS master driver of GP4000 series

Last Update: Aug. 23, 2012
Posted: Jun. 29, 2012

Thank you very much for your continuous use of Pro-face products.
We have confirmed that the following symptom occurs by some PLC at MODBUS TCP communication.
The symptom for this problem is indicated below.
We sincerely apologize for any inconvenience this may cause you.

Symptom

When ‘MODBUS IDA General MODBUS TCP Master Driver.’ and  ‘Schneider Electric SA MODBUS TCP master driver’ are used in GP4000 series, communication may be impossible and the following communication error may occur.

Error : RHAA065:PLC1: TCP : It is not completed to open. (xxx.xxx.xxx.xxx)

Subjected Product Combination

Applicable when the following products are used in combination.

Affected HMI models:
SeriesProduct Model
GP4000 Series

All models
(GP-4105G, GP-4105W, GP-4106G and GP-4106W are not affected.)


PLC Driver

Schneider Electric Industries MODBUS TCP Master Driver.

MODBUS IDA General MODBUS TCP Master Driver.

Cause and Measures

It was the problem of the controller chip in slave devices (PLC etc.).
If you have condition occurs, please contact our sales office in your region.
For contact information, please refer to the "Inquiry" page.

Inquiry

PLC connected may not be connectable by a maker's specification change (version or revision) etc.

Please use it after performing checking of operations in advance.